Loading...
BT Electric Upgrade DrawingsCKT AMP TRIP/FUSE AMP FRAME/PHASE DESCRIPTION ABCTOTAL SECTION 1 CT SECTION 1 800 800/3 MAIN BREAKER 50273 50273 50273 150819 TOTAL WATTS 50273 50273 50273 150819 TOTAL AMPS 419 419 419 419 SWITCHBOARD: MDP 800 AMPERE, 120/208 VOLT, 3 PHASE, 4 WIRE, FRONT ACCESSIBLE, NEMA4 ENCL., BOTTOM FEED, 22,000 AIC, SERVICE ENTRANCE RATED, CIRCUIT BREAKER STYLE DISTRIBUTION SWITCHBOARD WITH CECHA METERING COMPARTMENT, NEMA 4. SECTION 2 CKT AMP TRIP/FUSE AMP FRAME/PHASE DESCRIPTION ABCTOTAL 1 600 800/3 SWITCHBOARD DPB 28300 28300 28300 84900 2 400 800/3 SWITCHBOARD DPC 21973 21973 21973 65919 TOTAL WATTS 50273 50273 50273 150819 TOTAL AMPS 419 419 419 419 800 AMPERE, 120/208 VOLT, 3 PHASE, 4 WIRE, FRONT ACCESSIBLE, NEMA4 ENCL., BOTTOM FEED, 22,000 AIC, CIRCUIT BREAKER STYLE DISTRIBUTION SWITCHBOARD, NEMA 4. SWITCHBOARD: DPA CKT AMP TRIP/FUSE AMP FRAME/PHASE DESCRIPTION ABCTOTAL 1 200 200/3 HVAC: RTU MAIN 2 200 200/3 PANEL LP1 3 200 200/3 PANEL BASEMENT 4 200 200/3 PANEL OFFICE 5 200 200/3 PANEL LPE1 6 100 100/3 HVAC: RTU WOMENS LOCKER 7 100 100/3 HVAC: RTU MEN'S LOCKER 8 100 100/3 PANEL BASEMENT 2 9 100 100/3 EQUIPT: POOL PUMP 10 200/3 200/3 PANEL LP EXISTING PEAK DEMAND 28300 28300 28300 84900 TOTAL WATTS 28300 28300 28300 84900 TOTAL AMPS 236 236 236 236 SWITCHBOARD: DPB 800 AMPERE, 120/208 VOLT, 3 PHASE, 4 WIRE, FRONT ACCESSIBLE, NEMA4 ENCL., BOTTOM FEED, 22,000 AIC, CIRCUIT BREAKER STYLE DISTRIBUTION SWITCHBOARD, NEMA 4. TWO SECTIONS.